Home    |   About Us  |   Projects     Exports   |   Techno Tips   |   Products    |   Contact Us  
 

Air Cooling Unit (below 0°C)

Air Cooling Units for below 0°C application (SALSeries)

superfreezOPTIONAL FEATURES

  • Hot dip galvanized coil with steel pipe and steel fins.

  • Hot gas defrosting arrangement.

  • Custom Built coils for special applications.
Model No
No of Coils
No. of row Deeps
No of fans
Total Air flow M3/HR
KW/HP Per Fan
Capacities Kcal/HR/Deg. CTD
Capacities Kcal/HR/Deg. CTD
Over al Dimensions (without accumulator) (mm) (LxWxH)
3 Fins/Inch
4 Fins/Inch
Below 0 Deg. C
 
 
 
 
 
 
 
 
SAL-164
1
4
2
17,600
0.55/0.75
1775
1950
2360x865x1105
SAL-166
1
6
2
17,000
0.55/0.75
2270
2520
2360x865x1105
SAL-168
1
8
2
16,400
0.55/0.75
2900
3150
2360x865x1105
SAL-206
1
6
2
17,000
0.55/0.75
2775
3020
2810x865x1105
SAL-208
1
8
2
16,400
0.55/0.75
3400
3625
2810x965x1105
SAL-236
1
6
3
25,500
0.55/0.75
3800
4050
3310x865x1105
SAL-238
1
8
3
24,500
0.55/0.75
4565
4815
3310x965x1105
SAL-326
2
6
4
34,000
0.55/0.75
4540
5040
5650x865x1105
SAL-328
2
8
4
32,800
0.55/0.75
5800
6300
5650x965x1105
SAL-3210
2
10
4
32,000
0.55/0.75
7000
7400
5650x1065x1105
SAL-408
2
8
4
32,800
0.55/0.75
6800
7250
6550x965x1105
SAL-4010
2
10
4
32,000
0.55/0.75
8650
9080
6550x1065x1105
SAL-468
2
8
6
49,000
0.55/0.75
9130
9630
7120x965x1105
SAL-4610
2
10
6
48,000
0.55/0.75
10375
10775
7120x1065x1105
CAPACITY CORRECTION FACTORS FOR SUCTION TEMP.
-20deg. C -25deg.C -30deg.C -35deg.C -40deg. C
1.01 1.00 0.98 0.96 0.93
SAL-Front throw Low temp